Use este identificador para citar ou linkar para este item: http://repositorio.ufla.br/jspui/handle/1/15433
Título: A new power quality deviation index based on principal curves
Palavras-chave: Power system
Principal curves
Electric power quality
Data do documento: 2015
Editor: Elsevier Sequoia
Citação: FERREIRA, D. D. et al. A new power quality deviation index based on principal curves. Electric Power Systems Research, Lausanne, v. 125, p. 8-14, Aug. 2015.
Resumo: In this paper, a new power quality deviation index based on principal curves is proposed. The index provides a quantitative measure, which gives an idea of how much the monitored electrical signal has deviated from the nominal one. Differently of existing indices, the proposed index is a general index, i.e., it can be used for any type of disturbance in the monitored signal. In addition, the proposed index is used to perform a direct approach for detecting disturbances in power signals. This approach is able to detect the beginning and localize the disturbance by analyzing non-overlapping signal windows of one cycle of the fundamental component, leading to a simple method in terms of computational complexity.
URI: http://www.sciencedirect.com/science/article/pii/S0378779615000863
repositorio.ufla.br/jspui/handle/1/15433
Aparece nas coleções:DEG - Artigos publicados em periódicos

Arquivos associados a este item:
Não existem arquivos associados a este item.


Os itens no repositório estão protegidos por copyright, com todos os direitos reservados, salvo quando é indicado o contrário.